Every word the simulator uses, grouped by what kind of thing it is.
Most confusion comes from mixing the buckets up — a riser is not a part, and
rough-in is not a component.
Every station on the path does one of three jobs: it measures,
it protects, or it distributes. Once you know which job a part does,
its position in the chain is obvious.
The whole chain. Colour marks the job each station does. Notice there
are only three jobs — once you can name a part's job, you know where it sits.
Service drop / service entrance
The conductors running from the utility's pole to your house. "Drop" when it comes
overhead, "lateral" when it comes underground. This is the boundary — the utility owns
one side, you own the other.
Watthour meter (kWh meter)
Measures. Counts the energy you use so the utility can bill you. Owned and
sealed by the utility; you don't touch it. It sits before everything of yours, so
every kilowatt-hour that enters the house is counted.
Main breaker / main disconnect
Protects. One switch that kills power to the whole house, and trips if the
total current exceeds its rating. It also protects the service entrance conductors
behind it.
Panelboard (panel, load centre, breaker box)
Distributes. Takes the one incoming supply and splits it into many branch
circuits, each with its own breaker. Inside are the bus bars — metal strips the
breakers clip onto — plus a neutral bus and a ground bus.
Branch circuit
One breaker and the wiring it feeds. This is the unit everything is counted in:
"an eight-circuit house" means eight breakers, each running its own set of outlets or
lights. Circuit 1 on your schedule is one branch circuit.
Feeder
A run between two panels, rather than from a panel to outlets. It is the same idea
as a branch circuit but bigger, because it carries everything downstream of it.
Sub-panel
Distributes, again. A second panelboard fed by a feeder from the main. Used
when a part of the building is far from the main panel — a garage, a second floor, a
workshop — so you run one big cable instead of a dozen small ones.
Utility box / junction box / octagon box
The enclosure a splice or a device sits in. Every connection must be inside a box —
that is what stops a loose splice from starting a fire in a wall. An octagon box
is the eight-sided one used at ceiling lighting outlets; a utility box is the
rectangular one for switches and outlets.
Convenience outlet (CO)
An ordinary wall socket. Called a receptacle or "convenience outlet" on plans; in
everyday Philippine speech, a saksakan.
Special purpose outlet (SPO)
An outlet dedicated to one appliance — aircon, water heater, range. It gets its own
circuit and its own breaker, because sharing would overload the wire.
Lighting outlet
The point a light fixture connects to. Note it means the connection point,
not the lamp — this trips people up on plans.
Home run
The stretch of a circuit that goes back to the panel. On a plan it's the arrow with
the circuit number, marking where that circuit's cable leaves for the panelboard.
Ground rod / grounding electrode
Protects. A copper-clad rod driven into the earth, connected to the panel by
the grounding electrode conductor. It gives fault current and lightning a path into the
ground instead of through you.
Every connection lives in a box. That is the rule that stops a loose
splice starting a fire inside a wall. The shape tells you the purpose.
Why order matters. Meter before main breaker, main breaker before panel, panel
before circuits. Anything upstream of a protective device is unprotected — which is why
the service entrance conductors between the meter and the main breaker are kept as short
as the code allows.
2. The conductors
Hot goes out, neutral comes back, ground does nothing at all until
something breaks. Everything else — traveller, switched leg — is just a hot wire with a
job description.
One lamp, one switch. Follow the red: it stops at the switch and leaves
as blue. The white never passes through the switch at all, and the green does nothing
until there is a fault.
Hot (live, line, phase)
Carries voltage from the source. Touching it while grounded is what shocks you.
Red or black in Philippine practice. Switching and fuses always belong on the hot
side.
Neutral
The return path back to the source. It normally carries the same current as the hot,
so it is not safe to treat as dead — it is only near zero volts because it is
bonded to earth back at the service. White.
Ground (equipment grounding conductor)
Carries no current in normal operation. Its whole job is to give fault current a
low-resistance path back so the breaker trips fast. Green, or bare copper.
Switched leg (switch leg, load wire)
The hot wire after the switch — live only when the switch is on. Runs from
the switch to the fixture.
Traveller
The pair of wires running between two three-way switches. Either one may be live
depending on switch positions, which is exactly how three-way switching works.
Why "three-way" has nothing to do with three ways. Three
terminals: one common and two travellers. The switch always connects the common to
one traveller or the other — there is no off position. The lamp lights when both switches
happen to be looking at the same traveller.
Common (COM)
The odd terminal on a three-way switch — usually a darker screw. The switch connects
the common to one traveller or the other. Get the common wrong and the pair behaves
erratically instead of failing outright, which is why it's a hard fault to find.
Bonding
Deliberately connecting metal parts together so they sit at the same voltage. Boxes,
conduit and fixture bodies are all bonded to ground.
Conduit
The pipe conductors are pulled through — PVC or metal. It protects the wire
mechanically and lets you replace it later. Conduit fill is the rule limiting how
many conductors may share one pipe, so they can dissipate heat and still be pulled.
The single most important difference between a main panel and a
sub-panel. Neutral and ground are joined once, at the service. At a sub-panel the
neutral bus floats clear of the enclosure and the ground is its own conductor.
The one that actually hurts people: a switched neutral. If the switch interrupts
the neutral instead of the hot, the lamp turns on and off perfectly normally — but the
fixture stays live with the switch off. Someone changing a bulb gets shocked. It looks
correct and tests correct with a lamp. Only a voltage tester finds it.
3. The numbers
Almost everything traces back to one relationship: amps = watts ÷
volts. Work out the amps, pick a wire that can carry them, then pick a breaker that
protects the wire.
Ampacity
How much current a conductor can carry continuously without overheating. It is a
property of the wire, and it is the number the breaker is chosen to protect.
The breaker protects the wire, not the appliance
This is the idea that makes the whole table make sense. A 20 A breaker on 3.5 mm²
wire is not there to save your aircon — it is there to stop the cable inside your wall
from getting hot enough to burn. That is also why an oversized breaker is dangerous
while an oversized wire is merely expensive.
mm² and AWG
Two ways of stating conductor size. mm² is the actual cross-sectional area of copper
and is what Philippine practice uses; AWG is the American gauge system, where a
smaller number means a bigger wire.
Continuous load, and the 125% rule
A load running three hours or more without a break. It must be sized at 125% of its
rating — the same thing as keeping the conductor at or below 80% of its ampacity.
Lighting and aircon count; a rice cooker does not.
Pole (1P, 2P)
How many conductors the breaker interrupts. A two-pole breaker opens both wires at
once with a single handle, which is what a 230 V appliance circuit wants.
AT and AF
On Philippine plans, AT is ampere trip — the current at which it trips, the
number you actually size. AF is ampere frame — the physical body size the breaker
is built in. Several AT ratings share one AF.
Voltage drop
Voltage lost along a long cable run. Ampacity alone can approve a wire that is still
too thin over distance, which is why long runs get upsized. It matters far more on
low-voltage DC than on 230 V AC.
Not yet calculated by the simulator.
Connected load vs demand load
Connected load is everything added up. Demand load is what will realistically run at
once — always less, because you don't use every appliance simultaneously. Real service
sizing uses demand factors; the simulator uses connected load, which is the conservative
direction.
Why the table looks the way it does. Ampacity tracks copper area, so
the jump from 2.0 to 14 mm² is a sevenfold increase in metal for less than four times
the current — the extra is margin against heat.
mm²
AWG
Ampacity
Usual breaker
Typical use
2.0
14
15 A
15 A
Lighting
3.5
12
20 A
20 A
Outlets, small aircon
5.5
10
30 A
30 A
Aircon, water heater
8.0
8
40 A
40 A
Range, small service
14
6
55 A
50 A
Service entrance
Ampacities for THHN copper at 30 °C ambient.
Real installations derate for heat and for bundling — these are the starting figures,
not the final answer.
4. The drawings
None of these are hardware. Rough-in is a stage of work; the others
are kinds of drawing, each answering a different question about the same house.
Three sheets, three questions, one house. None of them is complete on
its own — which is why a permit set carries all three.
Rough-in
The stage before the walls close: conduit, boxes, and wire pulled through them. No
devices, no fixtures, no cover plates. Wires are left long and hanging on purpose so
there is slack for trim-out. Inspection happens here, while everything is still visible.
Trim-out
The stage after the walls and ceilings are finished: terminate the conductors, install
the switches, outlets and fixtures, fit the plates.
Lighting layout
Where. A floor plan showing lighting outlets, switches, and which switch
controls which light.
Power layout
Where, again — but for convenience outlets and special purpose outlets. Kept
on a separate sheet from lighting so neither becomes unreadable.
Legend
The key to the symbols. Non-negotiable on a real plan: symbols are not fully
standardised, so the legend is what makes the drawing mean anything.
Schedule of loads
The numbers. A table, one row per circuit, listing the load, current,
conductor, conduit and breaker. It is where the sizing is justified — the drawing shows
intent, the schedule shows the arithmetic.
Riser diagram / one-line diagram
How it all connects. A schematic of the whole service, from utility through
meter, main breaker and panel to the circuits. Not to scale and not in real positions.
Called "riser" because in a multi-storey building the service rises through the floors —
the name sticks even in a bungalow.
One-line (single-line)
The convention the riser is drawn in: a single line represents a run even when it is
two or three conductors, with tick marks giving the count. Drawing every conductor would
make the sheet unreadable.
Title block
The bordered strip carrying the project name, what the sheet shows, the scale, the
date and the sheet number. It's how a drawing stays identifiable once it's off your
screen.
How the sheets fit together. The layouts say where. The riser says how
connected. The schedule says how big. Any one alone is incomplete, which is
why a permit set includes all three.
5. The solar side
Size everything from consumption, never from panels. Work out the
watt-hours you use per day first; every other number follows from it.
The order matters as much as the parts. The inverter goes straight to
the battery with its own fuse. Its surge draw is many times what a controller’s load
terminals can pass.
Peak sun hours (PSH)
Not hours of daylight. It is the day's total solar energy re-expressed as hours at a
convenient full-strength 1000 W/m². The Philippines averages roughly 4.5–5.5; design on
4.5, or 4.0 if the rainy season matters to you.
Charge controller
Sits between panel and battery and regulates the charge. The panel's voltage is
higher than the battery's and swings all day, which is why it cannot feed a battery
directly.
PWM vs MPPT
PWM connects panel to battery and pulls the panel down to battery voltage,
wasting the difference. MPPT converts the excess voltage into extra current, so it
harvests meaningfully more from the same panel — typically 20–30% more, and the gap widens
in cold or cloudy conditions. MPPT costs more and is usually worth it above a few hundred
watts.
Depth of discharge (DoD)
How much of a battery you may actually use. Lead-acid gives about 50% before its life
drops sharply; LiFePO4 gives around 80%. This is why a lithium bank for the same job is
often little more than half the nameplate size.
Days of autonomy
How many days the bank should run the house with no sun at all. Two is common; three
for somewhere with long wet spells. It multiplies the bank size directly, so it is the
most expensive number in the design.
System voltage (12 / 24 / 48 V)
The battery bank's voltage. Higher voltage means less current for the same power, so
thinner and cheaper cable. Roughly: 12 V below 800 Wp, 24 V to about 2400 Wp, 48 V above
that.
Inverter
Turns bank DC into 230 V AC. Sized on the largest load running at once plus about 25%.
It connects straight to the battery with its own fuse — never to the charge
controller's load terminals, which are typically rated for only 10–20 A.
Surge rating
The brief overload an inverter tolerates at start-up. Motors — fridge, pump, aircon —
draw several times their running watts for a moment, so the surge figure matters more than
the continuous rating for those loads.
Wp (watt-peak)
A panel's output under standard test conditions. Real output is always lower; heat
alone costs a noticeable fraction on a hot roof.
Derate
The allowance for everything that loses you energy in practice — heat, dust, cable
losses, controller and inverter inefficiency. Around 25% is a common working figure, plus
about 10% for the inverter.
Off-grid, grid-tie, hybrid
Off-grid has no utility connection at all. Grid-tie feeds the grid and
has no battery, so it goes dead in a blackout. Hybrid has both battery and grid,
and can ride through an outage.
DC is less forgiving than the AC wiring elsewhere on this page. Polarity is not
optional — there is no neutral to save you. A battery bank can deliver hundreds of amps
into a dropped spanner, weld it in place and rupture the battery. And DC arcs do not
self-extinguish the way AC ones do, because AC crosses zero volts a hundred times a
second and DC never does — so every switch, fuse and breaker on the DC side must be
DC-rated. An AC-rated device can fail to break the circuit at all.